OFFICIAL XPF MAP PREVIEW

Siemens PAC2200 Modbus Register Map

Siemens PAC2200 Modbus map and register map with sample Modbus registers, register addresses, and power meter overview for engineers. Works with Modbus Monitor XPF (import directly) and includes downloadable CSV access in-app.

Power MeterModbus RTU / TCPPower, Current, Voltage, Energy, Status, Frequency
Open JSON previewRead device guideUse complete map in XPF

Register preview

This public preview shows 12 representative read-oriented signals. The complete official map is available in Modbus Monitor XPF.

SignalAddressTypeUnitCategory
Voltage UL1 N400002FLOAT32VVoltage
Current L1400014FLOAT32ACurrent
Apparent power L1400020FLOAT32kWPower
Secondary total of active energy im port400962DOUBLE64kWhEnergy
Frequency400056FLOAT32HzFrequency
Device diagnostics and device status400206UINT32-Status
Active tariff400212UINT32-General
Voltage UL2 N400004FLOAT32VVoltage
Voltage UL3 N400006FLOAT32VVoltage
Voltage UL1 L2400008FLOAT32VVoltage
Voltage UL2 L3400010FLOAT32VVoltage
Voltage UL3 L1400012FLOAT32VVoltage

Addressing note

Display address copied from the official XPF map preview. Modbus reference-number and zero-based offset conventions vary by device; verify the manufacturer manual before polling or writing.