OFFICIAL XPF MAP PREVIEW
Schneider Electric iEM3000 Modbus Register Map
Schneider Electric iEM3000 Modbus map and register map with sample Modbus registers, register addresses, and power meter overview for engineers. Works with Modbus Monitor XPF (import directly) and includes downloadable CSV access in-app.
Register preview
This public preview shows 12 representative read-oriented signals. The complete official map is available in Modbus Monitor XPF.
| Signal | Address | Type | Unit | Category |
|---|---|---|---|---|
| Voltage L1 L2 V | 403020 | FLOAT32 | V | Voltage |
| I1 phase 1 current A | 403000 | FLOAT32 | - | Current |
| Active power phase 1 kW | 403054 | FLOAT32 | kW | Power |
| Total active energy import Wh | 403204 | INT64 | kWh | Energy |
| Frequency Hz | 403110 | FLOAT32 | Hz | Frequency |
| Demand method | 403701 | UINT16 | kW | Demand |
| Digital input status bit only bit 1 is used | 408905 | UINT16 | - | Status |
| Digital input control mode | 407274 | UINT16 | - | General |
| MeterName:20 | 400029 | STRING | - | Identification |
| Protocol 0Modbus | 406499 | INT16 | - | Communication |
| Digital output control mode status | 409673 | UINT16 | - | Status |
| I2 phase 2 current A | 403002 | FLOAT32 | - | Current |
Addressing note
Display address copied from the official XPF map preview. Modbus reference-number and zero-based offset conventions vary by device; verify the manufacturer manual before polling or writing.