OFFICIAL XPF MAP PREVIEW

Carlo Gavazzi EM24 Modbus Register Map

Carlo Gavazzi EM24 Modbus map and register map with sample Modbus registers, register addresses, and power meter overview for engineers. Works with Modbus Monitor XPF (import directly) and includes downloadable CSV access in-app.

Power MeterModbus RTU / TCPEnergy, Voltage, Power Factor, Status, Frequency
Open JSON previewRead device guideUse complete map in XPF

Register preview

This public preview shows 12 representative read-oriented signals. The complete official map is available in Modbus Monitor XPF.

SignalAddressTypeUnitCategory
V L1 N300001INT32-Voltage
KWh TOT300063INT32kWhEnergy
Hz300056INT16-Frequency
PF L1300051INT16-Power Factor
Digital input status300769UINT16-Status
A L1300013INT32-General
Version code300771UINT16-Identification
V L2 N300003INT32-Voltage
V L3 N300005INT32-Voltage
V L1 L2300007INT32-Voltage
V L2 L3300009INT32-Voltage
V L3 L1300011INT32-Voltage

Addressing note

Display address copied from the official XPF map preview. Modbus reference-number and zero-based offset conventions vary by device; verify the manufacturer manual before polling or writing.

Need the complete map?

Open the pre-built Carlo Gavazzi EM24 map in Modbus Monitor XPF for the full register set, live polling, logging, and dashboards.

Open full map in XPF